These products feature: Digital readout for PT Supply and Deadband Settings, LED Indications for Raise / Lower Presignals,Undervoltage and Control Relay operation conditions, Continuously adjustable Time Delay Setting, Automatic Resetting after Voltage Correction, Single Pulse operation of Control Relays, Undervoltage Internal Blocking, Universal Power Supply, Password Protected, 4-20 rnA 0/P of P.T. Voltage for SCADA.(Optional)
Technical Specifications
Auxiliary Supply: 95-265V AC/DC, 10VA OR 110/ 230V AC ± 15% 50Hz, 10 VA
PT Supply: 110V AC 50Hz, 1.5 VA and readable on display
Low Voltage Setting: Adjustable between 90V to 121V and readable on display
High Voltage Setting: Adjustable between 95V to 140V and readable on display
Time Delay Setting: Fixed (Voltage Independent) Time Delay continuously adjustable from 10 to 180 Sees
Time Delay Resetting: Instantaneous resetting with voltage returning to deadband
T. Calibration: P. T. Value Difference can be adjust from – 10.0V to + 10.0V
Undervoltage Blocking: Internal blocking at 80V. Restoration at 85V
Control Relays: One pair of normally open potential free contacts of rating 5A at 240V AC or 24V DC resistive load for each Lower, Raise and Undervoltage control relays
Control Operation: Single Pulse operation with approx. 2 sees on time
Operating Temperature: 00C- 450C
Overall Dimensions (H-101): 92mm X 192mm X 110mm (H X W X D)
Panel Cutout (H-101): 90mm X 184mm (H X W)
Weight (H·101): 1.5 Kgs. (approx.)
Overall Dimensions (V-101): 360mm X 135mm X 145mm (H X W X D)
Panel Cutout (V·101): 330mm X 135mm (H X W)
Weight (V·101): 2.0 Kgs. (approx.)
For more Information: Email: sales@neutronics.co.in, Website: www.neutronics.co.in