Practical Application For On-Load Tap Changer Vibro-Acoustic Fingerprinting And Diagnostics

Advanced diagnostic tools have been developed that can reliably analyse and assess the condition of the OLTC...

The On-Load Tap-Changer (OLTC) is crucial for maintaining a stable voltage level in the electrical grid. With the help of the OLTC, the transformer turns ratio can be adjusted under load to account for voltage fluctuations. This mechanical switching process causes heating and arcing inside the OLTC. Consequently, various components will experience wear and tear over their lifetime. Increasingly advanced diagnostic tools have been developed that can reliably analyze and assess the condition of the OLTC.

The following example discusses a condition assessment based on combining a Dynamic Resistance Measurement (DRM) and a Vibro-Acoustic Measurement (VAM). While the DRM concentrates on the electrical characteristics when the load current is switched, the VAM focuses on the vibration pattern that the OLTC produces during the switching operation. The evaluation of the VAM results relies on comparing them with reference data such as a fingerprint or with sister units.

Measurement setup

The mechanical movements and arcing during an OLTC switching operation produce a wide frequency range of vibrations. The VAM allows these vibration patterns to be analyzed and compared with reference data and enables the mechanical condition of the tap-changer to be assessed. The signals are sampled at 250 kHz by the measurement system using integrated electronic piezo-electric (IEPE) acceleration sensors. This way, a non-invasive measurement can be performed on the transformer. This can even be done with the transformer in operation throughout the entire process.

VAM data evaluation

The signal recording covers the entire tap switch operation from motor start to finish [2]. The strongest signal is obtained during the diverter switch operation. As a first post-processing step a wavelet transformation is applied to the sensor signal. The so-called envelope curve is derived through integration in a typical frequency range from 10 kHz to 100 kHz and subsequent Gaussian filtering. The resulting curve reflects the energy of the raw signal in the defined frequency range. It can be used to compare reference data such as factory fingerprints or data from sister units [4]. Figure 4 illustrates a sensor’s raw signal and the corresponding envelope curve in dB over time.

Figure 4 Top: Raw signal from OLTC operation (left) and detailed diverter switch operation (right). Bottom: Corresponding envelope curve.

Figure 4 shows a detailed view of the diverter switch operation (highlighted). Attention should be paid to shifting peaks and less so to amplitude changes between the reference and the actual envelope curve to identify possible mechanical changes in the OLTC. The switching time analysis based on the envelope curve shows a considerably higher tolerance for external influences, making it much more suitable for comparisons.

Combining VAM and DRM

The VAM and DRM measurements of an OLTC represent mechanical and electrical time sequences, respectively, and provide an opportunity for a complimentary evaluation. Using the vibro-acoustic measurement, all OLTC components that produce sufficient vibrations are picked up and can be considered for evaluation. In contrast, a dynamic resistance measurement is only affected by operations that cause a change in the test current. Individual events in the DRM curve can typically be associated with the movement of diverter switch contacts. Thus, this information can map parts of the envelope curve to specific steps in the switching operation, such as opening or closing contacts.

Figure 5 shows the synchronous measurement result of an envelope curve and the corresponding DRM curve and illustrates which events are picked up by the VAM and DRM curve respectively.

Figure 5 Top: Envelope curve of diverter switch operation.
Bottom: Corresponding DRM curve.

Case study – Comparison of sister units

The VAM results of two 410 kV / 27 kV transformers are discussed in the following example. Both units have MR Oiltap® Type G diverter switch on-load tap changers.

Since fingerprints from the units under test aren’t available, comparing the two sister units is an effective approach for assessing the results. The following evaluation will only focus on the diverter switch operation.

The comparison of the envelope curves reveals that the vibration pattern of the two sister units matches almost perfectly, Figure 9.

Figure 9 Comparison of the envelope curves for a) odd and even and b) up and down traces.

Figure 9 depicts the tap switches from tap one to tap four. The markers indicate the start of the diverter switch operation. Ideally, each tap switch should be compared to its direct counterpart with the same parity and switching direction. Adding in the DRM data (Figure 10) helps map some of the VAM peaks to specific events like the operation of the main and auxiliary contacts.

Figure 10 Combination of VAM and DRM data from both OTLC units.

BIBLIOGRAPHY

  1. Mayo, L. Moisan “Effects of mounting on accelerometer performance” (Meggit, February 2011)
  2. Bengtsson “Acoustic Diagnosis of Tap Changers” (CIGRE 1996: 12-101)
  3. Viereck, A. Saveliev “Acoustic tap-changer analyses using continuous wavelet transformation” (IEEE, 2016)
  4. Foata, R. Beauchmin, K. Viereck, A. Saveliev and H. Hochmuth ““New Vibro-Acoustic Tap-Changer Diagnostic Method – First Results and Practical Experience” (CIGRE Session, Paris, 2016)

C. ENGELEN* (OMICRON electronics Germany),
J. HÄMMERLE (OMICRON electronics Austria),
C. PLATH (OMICRON electronics Germany),
M. FOATA (Maschinenfabrik Reinhausen Germany),
M. WOLFRAM (Maschinenfabrik Reinhausen Germany),
A. SAVELIEV (Maschinenfabrik Reinhausen Germany)